The Cooper & Hunter CH-HP65UIMRM

is a powerful 65 kW commercial air-to-water inverter heat pump providing up to 60 kW of cooling capacity. Equipped with R32 refrigerant, dual inverter rotary compressors, BMS compatibility and modular cascade capability for up to 16 units, it is designed for demanding commercial heating and cooling systems. With heating operation down to –20°C, cooling operation up to +52°C, and water temperatures up to 60°C, the CH-HP65UIMRM provides a flexible solution for large commercial and industrial HVAC projects.

Category:
Guaranteed Safe Checkout
Cooper & Hunter CH-HP65UIMRM Commercial Inverter Heat Pump

The Cooper & Hunter CH-HP65UIMRM is a high-capacity commercial air-to-water inverter heat pump designed for heating and cooling large commercial, industrial and multi-zone properties. It delivers a nominal 65 kW heating capacity and 60 kW cooling capacity, while its modular architecture allows several units to be combined for larger projects.

According to Cooper & Hunter, the CH-HP65UIMRM belongs to its commercial Inverter Modular Heat Pump range and uses environmentally friendlier R32 refrigerant, together with DC inverter technology for efficient capacity control. The system can operate in heating mode at outdoor temperatures down to –20°C and in cooling mode from –15°C to +52°C.

Key Features

65 kW Heating / 60 kW Cooling– High nominal capacity makes the CH-HP65UIMRM suitable for commercial properties, offices, hotels, apartment buildings and industrial HVAC applications.

DC Inverter Technology– The commercial modular range uses DC inverter technology for compressors and fans, allowing output to adapt to system demand and helping improve efficiency compared with conventional fixed-speed operation.

R32 Refrigerant– The CH-HP65UIMRM operates with R32 refrigerant, which is specified by Cooper & Hunter for this generation of modular commercial heat pumps.

Two Inverter Rotary Compressors– The two-compressor configuration provides the capacity required for demanding commercial applications while supporting controlled operation according to system load.

Operation Down to –20°C– The heat pump can provide heating at outdoor temperatures down to –20°C, while its cooling operating envelope extends up to +52°C.

Water Temperature up to 60°C– The system supports water heating temperatures of up to 60°C, expanding its potential use in appropriately designed hydronic heating systems.

Modular Cascade Operation– One of the major advantages of this commercial range is the ability to combine up to 16 units in a cascade. This enables designers to create considerably larger systems while matching capacity to the requirements of individual projects.

BMS Integration– Built-in compatibility with Building Management Systems (BMS) makes the heat pump suitable for professional commercial installations where HVAC equipment is centrally monitored and controlled.

Smart Control– The system supports an LCD SMART Display, weather-dependent operation, self-diagnostics and automatic system management.

Applications

The Cooper & Hunter CH-HP65UIMRM is designed primarily for large-scale hydronic HVAC systems. It is suitable for applications such as hotels, office buildings, retail facilities, apartment complexes, restaurants, warehouses, workshops and industrial premises. Its modular configuration is particularly useful for projects where heating and cooling demand may increase over time. Additional compatible modules can be incorporated into the system rather than replacing the entire heat-pump installation. Professional hydraulic and electrical system design is required. The exact operating performance will depend on outdoor temperature, required leaving-water temperature, water flow, system configuration and installation conditions.

Parameter Specification
Model CH-HP65UIMRM
Heat Pump Type Air-to-Water, Monoblock
Technology DC Inverter
Cooling Capacity 60.0 kW
Heating Capacity 65.0 kW
Rated Power Input – Cooling 20.8 kW
Rated Power Input – Heating 19.9 kW
EER 2.88
COP 5.51*
Seasonal Energy Efficiency – W35 155%
Energy Efficiency Class – W35 A++
Refrigerant R32
Compressor Type Inverter Rotary
Number of Compressors 2
Power Supply 380–415 V / 50 Hz / 3 Ph
Heating Operating Range –20°C to +40°C
Cooling Operating Range –15°C to +52°C
Maximum Water Temperature Up to 60°C
Sound Pressure Level 68 dB(A)
Sound Power Level 86 dB(A)
Water Pipe Connection 2″
Unit Dimensions (W × D × H) 2200 × 965 × 1675 mm*
Net Weight 686 kg
Cascade / Modular Operation Up to 16 units
BMS Connection Yes
Controller LCD SMART Display
Weather-Dependent Control Yes

Reviews

There are no reviews yet.

Be the first to review “Cooper & Hunter CH-HP65UIMRM”

Your email address will not be published. Required fields are marked *